Test method
How we test air conditioners
The uses we score and the tests we run on every AC: cool-down at 45 °C, power over an eight-hour night, bedroom noise, inverter and low-voltage running.
Every air conditioner we review goes through the same uses and tests below, in a real bedroom of an Indian flat, over four to six weeks of summer heat, on the unit we bought or borrowed. That is what makes the results comparable: a cool-down time or a night’s power use means the same thing for every AC on the site, though room sizes differ slightly and each review states the room it used.
Where a review turns units into a monthly bill, it states the tariff it used, so you can redo the sum with your own rate. Each test result in a review links back to the matching test on this page.
What we score
- Peak summer heat
- How quickly it cools a bedroom on a 45 °C afternoon, and whether it holds the set point afterwards instead of drifting up.
- Overnight bedroom use
- How quiet the indoor unit is at night and how steadily it holds the room temperature through an eight-hour night.
- Running cost
- How much electricity it draws once the room has settled and over a full night, which is what decides the monthly bill.
- Power cuts and low voltage
- Whether it starts and runs on a home inverter during a cut, and keeps cooling when the supply sags on summer evenings.
The tests
-
Cool-down, 34 to 24 °C
We start with the test bedroom at 34 °C, set the AC to 24 °C on turbo and time how long the room takes to reach 24 °C. Room size varies by review (130 to 160 sq ft), and each review states the room it used.
-
Cool-down at 45 °C outdoors
We repeat the 34 to 24 °C cool-down on afternoons when the outdoor temperature is 43 to 46 °C, the conditions north and central Indian homes see in May and June, and time it the same way.
-
Holds 24 °C at 45 °C outdoors
After the 45 °C cool-down we keep logging the room temperature for the next hour. Pass means the room stayed at the 24 °C set point; fail means it crept up while the compressor ran near full speed.
-
Power draw, settled at 24 °C
Once the room has settled at the 24 °C set point, we read the AC's power draw from a plug-in power meter on its supply. This is the draw you pay for through most of an evening.
-
Energy over an eight-hour night
We log the electricity the AC uses over an eight-hour night in the test bedroom with the same plug-in meter. One unit is one kWh, as on your electricity bill.
-
Indoor noise, low fan
We measure the sound level 1 metre from the indoor unit with the fan on its lowest speed, the setting most people sleep with.
-
Indoor noise, turbo
We measure the sound level 1 metre from the indoor unit in turbo mode, as it runs during a fast cool-down.
-
Runs on a 3 kVA home inverter
We switch the AC onto a 3 kVA home inverter as it would run during a power cut. Pass means it started and kept running without tripping the inverter.
-
Keeps cooling at 185 V or below
We run the AC with the supply dipped to 185 V, or to 180 V on some units (each review says which), the low end of what many Indian homes see on summer evenings. Pass means it kept cooling without tripping.